Sensor power supply |
19…30 V
|
Voltage state 1 guaranteed |
>= 15 V
|
Current state 1 guaranteed |
>= 1 mA
|
Voltage state 0 guaranteed |
<= 5 V
|
Current state 0 guaranteed |
<= 0.5 mA
|
Input impedance |
24000 Ohm
|
Insulation resistance |
> 10 MOhm 500 V DC
|
Maximum power dissipation in W |
4.3 W
|
DC typical filtering time |
4 ms
|
DC maximum filtering time |
7 ms
|
Paralleling of inputs |
No
|
Typical current consumption |
200 mA at 3.3 V DC
|
MTBF reliability |
362681 H
|
Protection type |
1 external fuse per group of channel0.5 A fast blow Without reverse polarity protection
|
Voltage detection threshold |
< 14 V DC sensor fault > 18 V DC sensor OK
|
Status LED |
1 LED (green)+32 channels indicator: 1 LED (green)module operating (RUN): 1 LED per channel (green)channel diagnostic: 1 LED (red)module error (ERR): 1 LED (red)module I/O: |